Fire Protection System – Camp Buehring, Kuwait
Client: U.S. Army (FMS Program)
Facility: TCF – C4 Facility (Building 404A)
Location: Camp Buehring, Kuwait
Prepared By: Engr. Kamal Ram (NBTC)
Standards: UFC 3-600-01, NFPA 13, NFPA 20, NFPA 72
Scope of Work
-
Repair & upgrade of wet-pipe fire suppression system serving Switch Room, TCF Room, and UPS/Battery Room.
-
System classified as Ordinary Hazard (UFC 3-600-01, Table 9-3) with density 8 mm/min (0.20 gpm/ft²) over 230 m² (2,500 ft²) for a 1-hour duration.
-
Full hydraulic re-calculation, zoning, and pump/tank integration carried out.
-
Designed for U.S. Army Corps of Engineers approval (AFCEE).
Hydraulic Calculations
-
Remote Area: 2,500 ft², ~20 sprinklers (Quick Response, K-8.0)
-
End Sprinkler Flow: 26 gpm @ 10.6 psi
-
Sprinkler Flow (Total): ~592.7 gpm
-
Hose Allowance: 250 gpm
-
Total System Demand: 842.73 gpm (~112% of rated pump capacity – UFC permits up to 140%)
-
Residual Pressure at Supply: 61.95 psi
Fire Pump & Water Supply
-
Diesel Fire Pump: 750 gpm @ 65 psi (Peerless, UL/FM listed, USA)
-
Jockey Pump: 10 gpm @ 75 psi (Grundfos, Europe)
-
Fire Water Tank: 200 m³ GRP (10m × 5m × 4m, Hi-Tank, Korea)
-
Pump House: 5m × 5m, ventilated & air-conditioned to NFPA 20 requirements
System Materials & Equipment
-
Sprinklers: Viking VK202-D, Concealed Pendent, K-115 (K=8.0), 68°C
-
Valves & Fittings: Giacomini (Italy), Viking (USA), Nibco OS&Y with supervisory switch
-
Steel Piping: ASTM A53 Sch 40 Black Steel (Al Jazeera – Oman)
-
Underground Piping: Ductile Iron, AWWA C151/A21.51 (Saudi – SADIP)
-
Accessories: Waterflow switches (Potter), Fire Dept. connection (Croker USA), Alarm Bell (Viking)
Compliance & Outcome
-
System complies with UFC 3-600-01, NFPA 13, NFPA 20, and NFPA 72.
-
Hydraulic calculations confirmed adequate flow and pressure with ~12% safety margin.
-
Full submittal package delivered: design drawings, hydraulic calc report, and equipment datasheets for AHJ/US Army approval.