top of page
Design of Automatic Fire Sprinkler System

An Automatic Fire Sprinkler System is designed to contain and control an unfriendly fire allowing your family the precious time needed to escape from danger and decrease the amount of damage to your valuables from heat and smoke. An Automatic Fire Sprinkler System is a network of water-filled pipes which starts at your domestic water service line and ends with strategically spaced fire sprinkler heads located throughout your home. The sprinkler heads are frangible bulbs filled with a liquid that, when heated, expand causing the bulb(s) to break and the system to release water. The water from the sprinkler head will cover the area where the fire is located and will continue to operate until the fire department can fully extinguish the fire.​​​​

Automatic Fire Sprinkler System Design Guidelines Videos
Join YouTube Channel "Design Fire Protection with Kamal Ram"

The four primary systems are the wet pipe system, the dry pipe system, the preaction system and the deluge system.

Wet Pipe System

The wet pipe sprinkler system is, in general, the most cost-effective, the most versatile as far as protection strategies and pipe installation are concerned, and the easiest to maintain.  Its cost effectiveness is based on its having fewer components, requiring less maintenance and testing and having fewer design restrictions than any of the other three types of systems.  Wet pipe systems are installed where temperatures will not fall below 40°F (4°C) and where one of the design objectives is to put water on a relatively small fire as quickly as possible.

In a wet pipe system, components are arranged in such a manner that, as soon as the heat from a fire operates the heat responsive element of an automatic sprinkler, the water is discharged through the sprinkler to the fire.  It is possible to design these systems for fire control – controlling a fire to the room or area of origin until the fire department arrives and extinguishes the fire; fire suppression – actually suppressing the fire; or life safety protection – as in residential occupancies.  The wet pipe system can also include additives such as antifreeze or foam concentrate.

Design issues relative to the wet pipe sprinkler systems would include the following:

  • Is there a possibility or potential for freezing anywhere the water-filled components are installed?

  • Is interior or exterior corrosion a factor to be concerned about?

  • What are the appropriate materials for a wet pipe system?

Dry Pipe System

When sprinkler systems are required in buildings, or areas of buildings, where the ambient temperature will not be maintained above 40°F (4°C) dry pipe systems are an option.  The dry pipe system is more expensive than the wet pipe system; requires more maintenance and testing (weekly, monthly, annually, and over its lifetime); and has additional design requirements beyond those of the basic wet pipe system.

Click here to read more...

Typical-layout-for-dry-and-wet-type-spri

Preaction System

The preaction system is similar to a dry pipe system. It has a similar valve, and in general the same pipe, fittings, alarm initiating devices, and automatic sprinklers.  In addition to the sprinkler system, however, the preaction system incorporates a detection system.  Preaction systems areusually less cost-effective than the dry pipe systems and require additional maintenance and testing as well as maintenance and testing of the detection system.

There are many types of detectors and detection systems that can be used with the preaction systems.  It is in the system designer’s best interest to work closely with the owner and the architect to utilize the type of detection system that is appropriate for each specific area or system.  An example of such an area is the data or computer room, where the products of combustion can do as much damage to sensitive equipment as the thermal damage from a fire or the resultant application of water.  In these rooms, an air sampling detection system may be more appropriate than smoke detectors.  The air sampling system may detect particles of combustion before the human eye or nose does and can send signals or warnings before there is actual smoke damage or a fire or before water is necessary.

Click to read more... 

fire-sprinkler-installation

Deluge System

Deluge systems are similar to preaction systems, in most cases utilizing the same valves, pipe, fittings, alarm initiating devices, automatic sprinklers, and detectors, although all of the sprinklers are open and do not include the heat responsive element.  Spray nozzles can be used in deluge systems instead of the open automatic sprinklers.  The difference between preaction and deluge systems is that with the sprinklers open at all times, neither air nor water can be maintained in the piping.  The deluge system requires a detection system to operate and signal the deluge valve, opening the valve and allowing water to flow through the piping and discharge through all of the sprinklers or nozzles simultaneously.

Deluge systems can be installed in warm or cold very high hazard areas and the primary objective is to put as much water on a fire as is required to contain or control a severe fire hazard as quickly as possible.  These systems are utilized where a large amount of water is necessary quickly such as in flammable and combustible dispensing operations, aircraft hangars, and transformers.  The deluge systems frequently include foam concentrates.

Design issues relative to the deluge system would include:

  • What is the appropriate detection system?

  • Is the water supply adequate and appropriate for all sprinklers flowing?

  • Where will the discharged water run to and does it require containment?

deluge system
image14

Sprinkler System Design Issues

As indicated above there are some design issues that are specific to the different types of systems.  However, there are design issues or considerations that apply to all sprinkler systems.  Some of these are as follows:

  • Is the water supply adequate?

  • What are the insurance requirements and will they impact the system design?

  • Will the system be designed with the minimum code compliance or will it be designed for what is best for the client to exceed the minimum requirements?

  • Has the proper hazard analysis been undertaken and have all of the hazards been identified properly and evaluated?

  • Have the automatic sprinklers that are appropriate for the hazards as well as the system been selected?

The type of sprinkler system must be determined early in the design process. That decision in turn has implications on the remainder of the system design, from hydraulic criteria to water supply and system components.  The owner’s or client’s operations, processes, and overall needs must be included in determining the type of system for a specific project.

Finally, long-term effects such as the cost of inspection, testing, and maintenance of the sprinkler and detection systems, as well as life expectancy of the pipe, fittings, and other components must be included in the overall evaluation.

Looped Sprinkler System

A sprinkler system in which multiple cross mains are tied together so as to provide more than one path for water to flow to an operating sprinkler and branch lines are not tied together.

loop and tree system

Gridded Sprinkler System

A sprinkler system in which parallel cross mains are connected by multiple branch lines. An operating sprinkler will receive water from both ends of its branch lines while other branch lines help transfer water between cross mains.

Gridded System

Classification of Occupancies

Select the hazard type according to NFPA-13 (refer to attached).


Light Hazard Occupancies: where the quantity and / or combustibility of contents I slow and fires with relatively low rates of heat release are expected. Examples: Educational, Hospitals, Institutional, Museums, Residential, restaurant seating areas etc.

Ordinary Hazard (Group 1): where combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not exceed 8 ft (2.4m), and fires with moderate rates of heat release are expected. Examples: Automobile parking and showrooms, bakeries, glass manufacturing, laundries, restaurant service areas etc.

Ordinary Hazard (Group 2): where combustibility and quantity of combustibles is moderate to high, stockpiles of content with moderate rates of heat release do not exceed 12 ft (3.66m) and stockpiles of contents with high rates of heat release do not exceed 8 ft (2.4 m) . Examples: Leather good manufacturing, Chemical plants, cereal mills, dry cleaners, Libraries -large stack rooms areas, machine shops, paper and pulp mills, repair garages, tire manufacturing, etc.

Extra Hazard (Group 1) : where the quantity and combustibility of contents are every high and dust, lint or other materials are present. Examples: Aircraft hangers, combustible hydraulic fluid, printing, rubber reclaiming etc

Extra Hazard (Group 2): where moderate to substantial amounts of flammable or combustible liquids are present. Examples: Flammable liquids spraying, open oil quenching, plastic manufacturing, varnish and paint dipping etc.

System Component Definitions

Branch Lines: The pipes supplying sprinkler, either directly or through or through springs, drops, return bends, or arm-overs.

Arm - Over: A horizontal pipe that extends from the branch line to a single sprinkler or a sprinkler above and below a ceiling.

Cross Mains: The pipes supplying the branch lines, either directly or through risers.

Feed Mains: The pipes supplying cross mains, either directly or through risers.

Riser Nipple : Vertical piece of pipe between the main and branch line.

Risers: The vertical supply pipes in a sprinkler system.

Sprig: A pipe that rises vertically and supplies a single sprinkler. 

PARTS+IDENTIFICATION+4_27_2017+BUILT+ENV
1470234050

Sprinkler Discharge Characteristics Identification

​Refer to Table 6.2.3.1 for Sprinkler Discharge Characteristics Identification

Table 6.2.3.1 Sprinkler DIscharge Charac

Sprinkler Temperature Ratings, Classifications and Color Coding's of sprinklers

Refer to Table 6.2.5.1 for Sprinkler Temperature Ratings, Classifications and Color Coding's of Sprinklers

Table 6.2.5.1 Temperature Ratings, Class

Pipe Material Specifications

Piping above ground for size upto 4 inches (100 mm) shall be Galvanized Iron, Seamless, Class’s’, Heavy duty - BS 1387 or according to Table 6.3.1.1. Pipe above 4” (100 mm) shall be Black Steel, Wrought Steel, Sch 40, Seamless or according to table 6.3.1.1.

Table 6.3.1.1 Pipe or Tube Material and Dimensions

Table 6.4.1 Fittings Materials and Dimensions

System Protection Area Limitations

​The maximum floor area on any floor to be protected by sprinklers supplied by any one sprinkler system riser or combined system riser shall be as follows:

System Protection Area

Protection Areas per Sprinkler

The protection area of coverage of the sprinkler shall be established by multiplying the S dimension by the L dimension, as follows: As = S x L

S Dimension
S Dimension
A = SXL_Page_1

Protection Area of Coverage and Maximum Spacing between Sprinklers

The maximum allowable protection area of coverage for sprinklers (As) shall be in accordance with value indicated in 

Table 8.6.2.2.1(a) for Light Hazard occupancies, Table 8.6.2.2.1(b) for Ordinary Hazard occupancies, Table 8.6.2.2.1(c) for Extra Hazard occupancies, Table 8.6.2.2.1(d) for High- Piled Storage.

Table 8.6.2.2.1(a) Light Hazard Coverage
Table 8.6.2.2.1(b) Ordinary Hazard Cover
Table 8.6.2.2.1(c) Extra Hazard Coverage
Table 8.6.2.2.1(d) High-piled Storage.pn

Maximum Distance from Walls

The distance from the sprinklers to wall shall not exceed on-half of the allowable maximum distance between sprinklers. The distance from the wall to the sprinkler shall be measured perpendicular to the wall.

figure-a10-2-5-2-2-nfpa13-600

Minimum Distance from Walls

Sprinklers shall be located a minimum of 4 inch (102 mm) from the wall

sidewall-minimum-distance-600

Minimum Distances between Sprinklers

Sprinklers shall be placed not less than 6 ft (1.8 m) on centre.

In-rack sprinklers shall be permitted to be placed less than 6 ft (1.8 m) on centre.

Distance below Ceilings

Under unobstructed construction, the distance between the sprinkler deflector and ceiling shall be minimum of 1 inch (25.4 mm) and maximum of 12 inch (305 mm) throughout the area of coverage of the sprinkler.

Under obstructed construction, the sprinkler deflector shall be located in accordance to below figure 8.6.4.1.1.3.

Figure 8.6.4.1.1.3 Vertical Changes in C

Sprinkler under Peak of roofs and Ceiling

Sprinkler under peak of roofs and ceiling shall be in accordance with below Figure 8.6.4.1.3 (a) and Figure 8.6.4.1.3 (b).

Figure 8.6.4.1.3.1 (a)
Figure 8.6.4.1.3.1 (b)
Table 8.6.4.1.4 Sprinkler under roof

Protection Area of Coverage and Maximum Spacing for Side Wall Sprinklers.

The maximum allowable protection area of coverage for sprinklers and maximum distance between them shall be in accordance with value indicated in Table 8.7.2.2.1.

Table 8.7.2.2.1 Protection and Maximum S

Extended Coverage Upright and Pendent Spray Sprinklers - Protection Areas and Maximum Spacing. Table 8.8.2.1.2.

Table 8.8.2.1.2 Extended Coverage Sprink

Protection Areas and Maximum Spacing for CMSA (Control Mode Specific Application) Sprinklers. Table 8.11.2.2.1

8.11.2.2.1 Large Drop Sprinklers

Protection Areas and Maximum Spacing for ESFR (Early Suppression Fast-Response) Sprinklers. Table 8.12.2.2.1

Table 8.12.2.2.1 Protection Areas and Ma

Sprinklers in Electrical Room

8.15.10 Electrical Equipments

Rated Pressure

System components shall be rated for the maximum system working pressure to which they are exposed but shall not be rated at less than 175 psi (12.1 bar) for components installed above ground and 150 psi (10.4 bar) for components installed underground.

Pressure Reducing Valves

If water pressure in excess of 175 psi (12.1 bar), a listed pressure reducing valve shall be installed and set for an outlet pressure not exceeding 165 psi (11.2 bar) at the maximum inlet pressure. 

Pressure gauges shall be led on the inlet and outlet sides of each pressure reducing valves.

A relief valve of not less than 13 mm in size shall be provided on the discharge side of the PRV to set to operate at a pressure not exceeding 175 psi (12.1 bar).

PRV installation1
Flanged-pressure-reducing-valve

Backflow Preventor Assembly

Backflow preventers provide a critical interface between a building's fire protection system and the water supply that feeds it. A backflow preventer is a device designed to ensure that water inside a building's fire sprinkler system flows in one direction only -- from the water main to the system's pipes.

Backflow Preventer Assy

Calculating Pipe Sizes

Pipe sizes shall be in accordance with Table 22.5.2.2.1 for Light Hazard Pipe Schedules, Table 22,5,3,4 for Ordinary Hazard Pipe Schedule, Table 22.5.3.7 for Upright Sprinklers Above and Pendent Sprinklers below a Ceiling and pipe sizes for extra hazard shall be hydraulically calculated (Table A.22.5.4 for reference purpose only).

Table 22.5.2.2.1 Light Hazard Pipe Sched
Table 22.5.3.4 Ordinary Hazard Pipe Sche
Table 22.5.3.7 Number of Sprinklers Abov
Table A.22.5.4 Extra Hazard Pipe Schedul

Sprinkler Discharge Patter (Figure A.8.5.5.1)

The discharge pattern for most sprinklers is fully developed at about a four foot distance below the sprinkler. ... A small portion of the discharge wets the wall behind the sprinkler. The discharge from sidewall sprinklers is less effective compared to upright and pendent sprinklers.

Figure A.8.5.5.1 Sprinkler Discharge Pat

Floor Control Valve Stations (also called Zone Control Valve Assembly)

Zone Control Valve is a system designed to separate the area in case of maintenance and to get the indication of fire zone on a combination of Butterfly valve, Flow Switch, Pressure Gauge and Test & Drain Valves.

Its main purpose it to regulate water flow in the designated “zones” or areas and in some buildings, by floors / levels, thus named zone control valve.

FLOOR-CONTROL-VALVE-ASSEMBLY-BLOG

Fire Protection Riser Assemblies

Fire protection riser assemblies are crucial components in a building's fire protection system. They are vertical pipes that distribute water from the building's main water supply to various parts of the building, including sprinkler systems, fire hose cabinets, and other fire suppression equipment.

Warehouse Riser System

Key Components of Fire Protection Riser Assemblies:

  1. Riser Pipe:

    • The main vertical pipe that carries water from the water supply to the fire protection devices in the building.

    • Typically made of steel, ductile iron, or CPVC, depending on the building code and specific application.

  2. Control Valve:

    • Installed at the base of the riser to control the flow of water into the system.

    • Common types include gate valves, butterfly valves, or ball valves.

    • Often equipped with a tamper switch to signal when the valve is closed, ensuring that it remains open during normal operation.

  3. Check Valve:

    • Prevents water from flowing back into the main water supply once it has entered the riser.

    • Ensures that the water pressure in the fire protection system is maintained.

  4. Pressure Gauge:

    • Installed on the riser to monitor the water pressure within the system.

    • Typically located above the control valve and check valve to provide a reading of the pressure within the riser.

  5. Flow Switch:

    • Detects the flow of water through the riser and sends a signal to the fire alarm control panel.

    • Activated when water flows through the system, such as during the operation of a sprinkler or a fire hose.

  6. Test and Drain Assembly:

    • A combination of a drain valve and a test valve that allows for testing the system's functionality and draining water from the riser.

    • Often includes an inspector’s test valve to simulate the operation of a sprinkler head.

  7. Alarm Valve (for Wet Systems):

    • Controls the flow of water into the wet pipe sprinkler system.

    • When a sprinkler head opens, the alarm valve allows water to flow into the system and activates the water motor gong or electric alarm to signal the fire alarm.

  8. Air Vent (for Dry Systems):

    • Releases air trapped in the riser in dry-pipe or pre-action sprinkler systems to prevent water hammer and ensure smooth operation when the system is activated.

  9. Fire Department Connection (FDC):

    • A connection point on the riser that allows the fire department to supply additional water to the system in case of a fire.

    • Typically located on the exterior of the building and connected to the riser via a pipe.

Warehouse Riser System2

TYPICAL FIRE PROTECTION RISER ASSEMBLY

Figure A.9.2.3.4.4(b) Examples of Accept
Table 9.2.2.1 (b) Maximum Distance Betwe
Figure A.9.2.3.4 Distance from sprinkler
Table 9.1.2.1 Hanger Rod Sizes
Figure A.9.2.3.4 (a) Distance from Sprin
Table 9.1.3.10.1 Minimum Bolt Size for C

Branch Pipe shall not exceed 8 Sprinklers.

On a branch pipe we can only install maximum up to 08 Nos. of sprinklers according to KFD regulations

Maximum 08 sprinkler on a branch lines_P

Sprinkler Head installation without false ceiling:
Distance between slab and sprinkler shall be minimum 1" (25 mm) and maximum 12" (300 mm)

Upright Sprinklers

Pendent sprinkler heads installation when false ceiling height is less than 80 cm.

Pendent sprinkler installation less than

 Two layer sprinkler heads when false ceiling height is more than 80 cm.

Typical two layer sprinkler installation

Install one sprinkler below any duct or cable tray when width is more than 80 cm below.

Typical Sprinkler installation below duc

NUMBER OF SPRINKLERS ON A BRANCH LINE

According to NFPA 13, Branch lines shall not exceed eight sprinklers on either side of a cross main

Number of Sprinkler on Branch Line
Number of Sprinkler on Branch Line-NFPA 13
Number of Sprinkler on Branch Line-Formula

Installation Control Valve (Also called Alarm Check Valve)

An alarm check valve is basically a check valve with an alarm port. The main purpose of the alarm check valve is to ring a mechanical bell called a water motor gong. The valve should, (if properly maintained), help hold the system pressure steady and reduce the possibility of false alarms.

The alarm check valve is a water flow alarm device designed for vertical installation in the main supply to a wet pipe sprinkler system. When a flow of water from the system equals or exceeds that of a single sprinkler, the valve is to actuate a fire alarm.

Local alarms shall be provided on all sprinklers system having more than 20 sprinklers.

20151229_092908
Alarm Check Valve 2
ICV - Viking
ICV Working
ICV Installation

Retard Chamber Purpose : A chamber that delays the alarm signal to avoid false alarms due to pressure surges.

Fire Department Connection

A fire department connection shall be provided as described in accordance with Figure 8.17.2.1. Pipe size shall be a minimum 4 in (100 mm) for fire engine connections and 6 in (150 mm ) for fire boat connections.

The FDC shall be on the system side of the water supply check valve.

For multiple systems, the FDC shall be connected between the supply control valves and the system control valves.

The FDC shall be on the street side of the building. A listed check valve shall be installed in each fire department connection.

There shall be no shut-off valve in the FDC piping.

FCS
FDC-and-Check-Valve-Illustration-Resized
FDC

System Main Drain

Auxiliary drains shall be provided where there is change in piping direction prevents drainage of system piping through the main drain valve.

Provision for flushing:

All sprinkler systems shall be arranged for flushing. Readily removable fittings shall be provided at the end of all cross mains. All cross main shall terminate in 31.8 mm or larger. All branch lines or gridded system shall be arranged to facilitate flushing.

Table 8.16.2.4.2 Drain Size

VENT IN AUTOMATIC SPRINKLER SYSTEM​

In an automatic sprinkler system, vents play a crucial role in ensuring the proper operation and efficiency of the system. Here are the primary types of vents used in automatic sprinkler systems:

1. Air Release Valves (Air Vents):

  • Purpose: These are installed to release trapped air within the sprinkler piping. Trapped air can cause issues like air pockets, which may lead to water hammer, delayed water discharge, and potential damage to the system.

  • Location: Typically, these valves are installed at the highest points of the sprinkler piping network where air naturally accumulates.

  • Function: When air builds up in the system, the air release valve automatically opens to release it, ensuring the piping remains filled with water and ready for immediate activation.

2. Automatic Air Vents:

  • Purpose: These are similar to air release valves but are designed to continuously vent air from the system, even during operation. This is particularly important in wet-pipe sprinkler systems.

  • Location: Installed on the sprinkler riser or at strategic points within the piping system.

  • Function: These vents help to maintain a water-filled system, which is crucial for the quick activation of sprinklers in the event of a fire.

3. Ventilation in Dry Pipe Systems:

  • Purpose: In dry pipe sprinkler systems, which are filled with air or nitrogen, a vent is used to release the air from the system when water is introduced (e.g., during a fire).

  • Location: Often found near the dry pipe valve or at high points in the system.

  • Function: When the system is triggered, the vent allows air to escape, enabling water to fill the piping quickly and reach the sprinklers.

4. Manual Air Release Vents:

  • Purpose: These are used for manually venting air from the system during maintenance or testing.

  • Location: They are often installed at the end of sprinkler lines or on the highest point of the system.

  • Function: Maintenance personnel use these vents to purge air that may have accumulated during system filling or after maintenance.

5. Pressure Relief Valves:

  • Purpose: Although not a vent in the traditional sense, pressure relief valves are installed to prevent over-pressurization in the system by releasing excess pressure.

  • Location: Typically located near the pump or at strategic points in the system.

  • Function: These valves help to maintain the system's integrity by venting excess pressure that could otherwise cause damage.

Importance of Vents:

  • Ensuring that the sprinkler system is free of air pockets and operating at the correct pressure is vital for its responsiveness and effectiveness in fire situations.

  • Proper venting also helps in preventing corrosion inside the piping, which can be caused by trapped air or water with high oxygen content.

In summary, vents in an automatic sprinkler system are essential for maintaining system readiness, preventing damage, and ensuring that water is delivered promptly when a fire occurs.

Dry-Riser-scaled
frame_2_delay-1s

Automatic Sprinklers shall be installed in:


A) Basement used as a car parks or storage occupancy if the area exceed 200 m2.

B) Multilevel basements. 

C) Any room or other compartment of a building exceeding 1125 m2 in area.

D) Departmental stores or shops, if the aggregate covered area exceed 500 m2.

E) All non-domestic floors of mixed occupancy which constitute a hazard and are not provided with staircase independent of the remainder of the buildings.

F) Godowns and warehouses as considered necessary.

NFPA 13 typically does not require sprinklers in open parking structures that are well-ventilated and have at least 50% of the wall area open to the atmosphere. These are generally considered low hazard due to natural ventilation.

Open Parking Garages:

If the parking area is classified as an open parking garage (per the International Building Code (IBC) and NFPA 88A), it may not require sprinklers. Open parking garages are designed to be naturally ventilated.

 

Enclosed Parking Garages:

Enclosed parking garages generally require sprinklers as they are considered more prone to fire hazards due to limited ventilation and the potential accumulation of flammable vapors.

NFPA 13: According to NFPA 13, K5.6 sprinklers (also known as standard orifice sprinklers) are generally suitable for ceiling heights up to 12 feet (3.7 meters) in light and ordinary hazard occupancies. However, the actual height can vary based on specific design criteria, including the type of hazard, the sprinkler spacing, and the ceiling configuration.

High Ceiling Applications:

For higher ceilings, larger orifice sprinklers with higher K-factors (e.g., K8.0 or K11.2) are often recommended to ensure adequate water distribution and pressure.

International Experience:


A) 55% of fires were extinguished by the operation of two or less sprinkler heads.

B) 80% of fires were extinguished by the operation of eight or less sprinklers.

C) 90% of fires were extinguished by the operation of 18 or less sprinkler heads.
 
D) Sprinkler coverage for the fire protection of occupancies has full legislative as well as insurance supports.

Testing & Commissioning Procedure for Automatic Sprinkler Systems

1. Pre-Commissioning Stage

1.1 Documentation & Approvals

  • Verify approved IFC (Issued for Construction) drawings and specifications.

  • Confirm that shop drawings and hydraulic calculations are reviewed and approved by AHJ.

  • Ensure material submittals (sprinklers, valves, hangers, alarms, etc.) are approved.

1.2 Visual Inspection

  • Check sprinklers are correctly located and installed per NFPA 13 spacing rules.

  • Verify sprinkler orientation (upright/pendent/sidewall).

  • Ensure sprinklers are free from paint, grease, and physical damage.

  • Confirm that sprinkler clearance is maintained (≥18 in. below deflector for storage).

  • Verify that pipes are supported by proper hangers, seismic bracing, and sway bracing.

  • Check that all control valves (OS&Y, Butterfly, Check, and PRV) are installed, labeled, and accessible.

  • Confirm drain and test connections are installed at the correct locations.

2. Hydrostatic Testing (NFPA 13 – §25.2.1)

2.1 Preparation

  • Isolate sprinkler system section by section if necessary.

  • Fill the system with water slowly, venting all trapped air at high points.

2.2 Test Parameters

  • Apply a hydrostatic pressure of 200 psi (13.8 bar) for 2 hours
    OR

  • 50 psi (3.4 bar) above the maximum system working pressure, whichever is higher.

2.3 Acceptance Criteria

  • No visible leakage.

  • No pressure loss during the test duration.

3. Flushing of Piping (NFPA 13 – §16.10.4.2)

  • Flush underground mains and risers before connecting to sprinkler system.

  • Minimum flushing velocity: 10 ft/sec (3 m/s).

  • Use temporary outlets with hoses discharging to open drains.

  • Collect debris in strainer or screen during flushing.

  • Continue until water is clear and free of foreign matter.

4. Functional Testing

4.1 Waterflow Alarm Test

  • Open inspector’s test connection at the most remote point.

  • Verify:

    • Water motor gong operates audibly.

    • Electric waterflow alarm activates and signals at FACP.

    • Alarm time ≤ 90 seconds.

4.2 Supervisory Alarm Test

  • Close each control valve in turn.

  • Confirm supervisory signal is received at FACP.

  • Confirm tamper switches reset after reopening valves.

4.3 Pressure Reducing Valves (PRVs)

  • Simulate design flow condition.

  • Confirm outlet pressure does not exceed design limit.

4.4 Pressure Relief Valves

  • Test operation at rated set pressure.

4.5 Fire Department Connections (FDC)

  • Hydrostatic test FDC piping to 200 psi for 2 hours.

  • Verify check valves and clappers operate correctly.

  • Confirm signage and caps are installed.

5. System Commissioning

5.1 Zone Testing

  • For high-rise systems, test each floor zone separately.

  • Confirm waterflow and alarm activation per zone.

  • Verify isolation valves for each zone are labeled and operational.

5.2 Integrated Testing

  • If system is connected to fire pump, confirm:

    • Sprinkler demand is achieved during pump operation.

    • Flow switches activate within allowable time.

  • If system is connected to fire alarm, confirm:

    • Sprinkler system alarms appear at central fire alarm panel.

    • Signal transmission to monitoring station (if required) is verified.

5.3 AHJ Witness Test

  • Conduct final testing in the presence of Authority Having Jurisdiction (AHJ) / Fire Marshal.

  • Provide all certificates, drawings, and test records.

6. Post-Commissioning Documentation

  • Submit Contractor’s Material & Test Certificate for Aboveground Piping (NFPA 13 Annex A).

  • Provide hydraulic calculation sheets, as-built drawings, and valve chart.

  • Prepare O&M Manual including:

    • Manufacturer data sheets.

    • Testing records.

    • Maintenance schedule (as per NFPA 25).

7. Maintenance Handover (NFPA 25 Reference)

  • Educate facility team on inspection, testing, and maintenance requirements:

    • Monthly valve inspections.

    • Quarterly alarm testing.

    • Annual waterflow test.

    • 5-year internal pipe inspection.

Key Deliverables

  • Hydrostatic Test Report

  • Flushing Test Report

  • Alarm & Supervisory Test Reports

  • PRV & FDC Test Records

  • Final Commissioning Certificate signed by AHJ

Automatic Sprinkler System – FAQs 

Q1. What is the purpose of an automatic sprinkler system?
A sprinkler system is designed to automatically detect and suppress fires in the early stage by discharging water over a defined area, preventing fire spread and protecting life and property.

Q2. What are the main types of sprinkler systems under UAE Fire Code?

  • Wet pipe systems

  • Dry pipe systems (for refrigerated/freezing areas <4°C)

  • Pre-action systems (single or double interlock, for sensitive occupancies)

  • Deluge systems (open nozzles, hazard-based discharge)

Q3. How are occupancies classified for sprinkler design?

  • Light Hazard – low combustibles, low heat release (offices, schools, residences)

  • Ordinary Hazard Group 1 – medium combustibles, low storage (<2.4m) (restaurants, hotels, retail)

  • Ordinary Hazard Group 2 – medium-high combustibles, higher storage (industrial, printing, workshops)

  • Extra Hazard Group 1 & 2 – high combustibles, industrial uses, flammable liquids/gases

Q4. What are the design densities for sprinklers?

  • Light Hazard: 0.10 gpm/ft² over 1,500 ft²

  • OH-1: 0.15 gpm/ft²

  • OH-2: 0.20 gpm/ft²

  • EH-1: 0.30 gpm/ft²

  • EH-2: 0.40 gpm/ft²

Q5. What are Civil Defence requirements for dry sprinklers?

  • Must discharge within 60 seconds.

  • Not allowed to be gridded.

  • Used in refrigerated/freezer areas.

Q6. Where are pre-action systems required?

  • Data centers, telecom rooms, lift machine rooms, high voltage electrical areas – where accidental discharge is catastrophic.

Q7. What is required for deluge systems?

  • Protects LPG tanks, transformers, tunnels, conveyors.

  • Open nozzles with hydraulic design to cover hazard.

  • Activated by detection (heat, gas, flame) or manually.

Q8. What is the difference between single-interlock and double-interlock pre-action systems?

  • Single interlock: water enters sprinkler piping only after detector activation.

  • Double interlock: requires both detector activation & sprinkler head operation.

Q9. Where are deluge sprinkler systems required?
For hazards such as LPG tanks, cable tunnels, transformers, conveyors, and fuel/oil storage.

Q10. What is the maximum spacing between sprinklers?
Based on K-factor, hazard, and design density. Typically:

  • Light hazard: ≤15 ft (4.6m).

  • Ordinary hazard: ≤12 ft (3.7m).

  • Extra hazard: ≤10 ft (3.0m).

Q11. What are the pipe material requirements?

  • Steel pipes (galvanized/black).

  • CPVC permitted for light hazard residential, subject to Civil Defence approval.

Q12. What are the testing requirements for sprinkler systems?

  • Hydrostatic pressure test at 200 psi (13.8 bar) for 2 hrs.

  • Flow test at hydraulically remote point.

Q13. What signs/markings are mandatory for sprinklers?

  • Floor control valves.

  • Zone identification tags.

  • Hydraulic design information plate.

Q14. What materials are permitted for sprinkler piping?
Only listed/approved fire protection materials (steel, CPVC, copper, ductile iron).

Q15. Can galvanized steel be used?
It is permitted but restricted in some systems (e.g., MIC concerns in wet pipe).

Q16. Are CPVC pipes approved?
Yes, but only in light hazard occupancies and per manufacturer’s listing.

Q17. What are the standards for valves?
Control and check valves must be listed, supervised, and accessible.

Q18. Can plastic pipes be used in concealed spaces?
Yes, if listed and properly protected from mechanical damage and chemicals.

Q19. What type of fittings are allowed?
Only listed fire protection fittings (grooved, threaded, welded).

Q20. What are the requirements for pressure gauges?
They must be installed at risers, pumps, and system outlets.

Q21. Are backflow preventers required?
Yes, per local plumbing codes and NFPA 13 cross-connection control.

Q22. What is required for spare sprinklers?
Minimum 6, 12, or 24 spare heads depending on system size.

Q23. Do system components require UL/FM listing?
Yes, all sprinklers, pipes, and valves must be UL/FM listed or approved.

Q24. What is the minimum sprinkler-to-ceiling distance?
1–12 in. depending on sprinkler type (pendent, upright, sidewall).

Q25. What is the maximum spacing between sprinklers?
15 ft typical for light/ordinary hazard; may vary for storage.

Q26. Can sprinklers be installed near beams?
Yes, but spacing must meet obstruction rules (beam depth/spacing).

Q27. How far should sprinklers be from walls?
Minimum 4 in., maximum 7½ ft (standard spray).

Q28. Are sprinklers required in small closets?
Not in some residential/light hazard occupancies, subject to exemptions.

Q29. Can sprinklers be installed in concealed spaces?
Yes, but may be exempt if concealed/limited combustible construction.

Q30. What are installation requirements for residential sprinklers?
Must be installed per listing and often closer to ceilings (deflector 1–4 in.).

Q31. Can sprinklers be painted?
No, only manufacturer-applied coatings are allowed.

Q32. Are sprinklers required in elevator machine rooms?
Yes, unless exemptions apply (machine-room-less elevators with protection).

Q33. What about obstructions like ducts or light fixtures?
Sprinklers must be located/added so spray is not blocked; NFPA 13 provides clearance tables.

Q34. What materials can be used for hangers?
Only listed hangers, rods, and supports for fire protection service.

Q35. What is maximum spacing of hangers for steel pipe?

  • 1 in. → 12 ft

  • 2 in. → 12 ft

  • 3–5 in. → 15 ft

  • 6–8 in. → 15 ft

Q36. How about CPVC pipe?
Spacing per manufacturer’s listing (often shorter).

Q37. Are seismic bracing requirements included?
Yes, for pipe ≥2½ in. in seismic regions.

Q38. What types of seismic braces are used?
Lateral, longitudinal, and 4-way sway braces.

Q37. Can pipe rest directly on ceiling grids?
No, it must be independently supported.

Q38. Are powder-driven fasteners allowed?
Yes, if listed for fire protection.

Q39. What rod sizes are required?
Minimum ⅜ in. for ≤4 in. pipe; ½ in. for larger.

Q40. Are hangers required near fittings?
Yes, within 3 ft of elbows and other changes in direction.

Q41. Do branch lines need seismic bracing?
No, only mains and larger runs, but restraints may be required.

Q42. What are the two main design methods?
Density/area method and room design method.

Q43. What is the minimum design area for light hazard?
1,500 sq. ft (can reduce with quick-response).

Q44. What about ordinary hazard?
1,500 sq. ft (OH1 & OH2).

Q45. How is storage designed?
By commodity class (I–IV, plastics), height, and sprinkler type.

Q46. What is the density for light hazard?
0.10 gpm/ft² over 1,500 ft².

Q47. What is the density for ordinary hazard?
0.15–0.20 gpm/ft² depending on OH1 or OH2.

Q48. What is the required safety margin?
Supply must exceed demand (often 10% or 5 psi margin).

Q49. What is the minimum pressure for sprinklers?
7 psi at the most remote head (standard spray).

Q50. How is hose stream allowance calculated?
250 gpm for light/ordinary, higher for storage/extra hazard.

Q51. Can quick-response sprinklers reduce design area?
Yes, up to 40% reduction in light hazard.

DCD Exam Question Bank Automatic Sprinkler System

DCD Mock Exam Automatic Sprinkler System

bottom of page