top of page
UAE Fire Protection System Design Guidance

Fire protection systems in the United Arab Emirates are governed by the UAE Fire & Life Safety Code of Practice issued by Civil Defence authorities to ensure the safety of occupants, protection of property, and continuity of building operations during fire emergencies. These guidelines outline the fundamental design principles for systems such as automatic sprinklers, wet and dry risers, fire hydrants, hose reel networks, fire pumps, and specialized suppression systems based on occupancy hazard classification and building characteristics. The purpose of this section is to provide a practical technical overview of key fire protection requirements commonly applied in UAE projects to support architects, developers, and engineers during planning and coordination stages. Detailed system design should always be carried out in accordance with the latest Civil Defence approved regulations and project-specific approval requirements.

UNITS

Fire protection system design commonly uses a combination of SI and non-SI units for pressure, volume, and flow calculations. Understanding these units helps ensure correct interpretation of hydraulic requirements and coordination with international fire protection standards such as NFPA and UAE Civil Defence practices.

Pressure

  • 1 bar = 14.5 psi

  • 1 psi = 0.0689 bar

Volume

  • 1 US gallon = 3.785 liters

  • 1 liter = 0.264 US gallons

  • 1 cubic meter = 1000 liters

  • 1 cubic meter = 264.17 US gallons

Flow

  • 1 gallon per minute (GPM) = 3.78 liters per minute (LPM)

These units are widely used in sprinkler hydraulics, fire pump sizing, storage tank calculations, and hydrant system design.

Hazard Classification for Sprinkler Protection
Hazard Class.png
Fire Hose Systems (Class I, II & III)
Fire Hose System Types.png
Fire Hose System Classification (Typical Applications)
Fire Hose System Applications.png
Fire Pump Requirements (Typical UAE Civil Defence Practice)
Fire Pump Requirements.png
Typical Vertical Turbine Fire Pump Arrangement (Concept Illustration – NFPA 20 / UAE Practice)

Typical Vertical Turbine Fire Pump Arrangement – Concept illustration based on NFPA 20 design practice. Final configuration shall comply with UAE Civil Defence requirements.

Verticle Turbine Fire Pumps1.png
Typical Horizontal Fire Pump Arrangement (NFPA 20 / UAE Practice Concept Illustration)

Typical Horizontal Fire Pump Arrangement – Concept illustration based on NFPA 20 design practice. Final installation shall comply with UAE Civil Defence requirements.

Horizontal Fire Pump1.png
Minimum Fire Pump Pipe Size Guidance (NFPA 20)

Pipe sizes summarized from NFPA 20 guidance commonly adopted in UAE fire pump design practice. Final sizing shall comply with Civil Defence approval requirements.

Table 4_28 NFPA 20.png

Fire water tank arrangements shall comply with UAE Fire & Life Safety Code requirements and Civil Defence authority approvals. Table above summarizes common design provisions used in practice.

Fire Water Tank.png
Isolation / Section Control Valves
Isolation Valves.png
Check Valves
Check Valves.png
Dry Riser Systems (Typical UAE Civil Defence Practice)
Dry Riser System.png
Fire Hose Reel Systems (Typical UAE Civil Defence Practice)
Fire Hose Reel System.png
Combined Dry Riser and Hose Reel System Arrangement (Typical UAE Practice)
DRP AND HRP_Page_1.png
Wet Riser Systems
Wet Riser System.png
Typical Fire Hose Cabinet Location Requirements
FHC Locations.png
bottom of page